STANCOR OIL-MINDER PUMP SPECIFICATION
MODEL O/M SE-50 ELV
ELEVATOR TYPE SYSTEM
GENERAL SPECIFICATION:
Provide pump and control systems capable of pumping water while containing oil. The system shall function automatically and shall provide for an alarm and separate LED lights in the event of (a) the presence of oil in the sump, (b) high liquid in the sump, or (c) high amps or a locked rotor condition. In addition, LED lights shall be provided for (1) power and (2) pump run function. An alarm that sounds only in the event of a high liquid condition or does not separately identify the above five functions shall not be acceptable.
PUMP SPECIFICATION:
The pump shall be a submersible type, capable of pumping up to 37' TDH and 74 GPM. The pump shall be approved to UL 778 standards and shall include thermal and overload protection. The motor shall be rated 1/2 H.P., 1 phase, 115V and capable of operating continuously or intermittently. The motor housing shall be constructed of #304 stainless steel and mechanical seats shall be housed in a separate oil-filled compartment.
CONTROL SPECIFICATION:
The main control shall be approved to UL 508 standards and housed in a gasketed Nema 4X enclosure with a see-through window for observation of operating functions. The control shall be equipped with an 8-pin twist lock receptacle, dual solid state Oil-Minder relays with variable sensitivity settings, an over current relay, self-cleaning stainless steel sensor probe, high decibel warning horn with alarm silencing switch, dual floats, clearly marked terminal board and remote monitoring contact. A Nema 4X junction box with 8-pin twist-lock electrical receptacle and 25' (additional lengths available in 25' increments) of mating 8 conductor cable shall be provided. All cables between the pump and junction box shall be 16' long and the cable and plug from the control unit shall be 8' long. The control unit, junction box, pump, floats and sensor shall be factory assembled as a complete, ready-to-use system and shall be tested and approved as a complete system by a nationally recognized testing laboratory such as ENTELA. The system shall allow for the main control to be located outside of the elevator hoistway to be monitored for all functions without having to enter the elevator shaft.
|